PN-VPC
ELECTRONIC/PNEUMATIC-TRANSDUCER
PRODUCT DATA
APPLICATION
An E/P Transducer accepts a proportional voltage signal
from an electronic controller and converts it into a pro-
portional pneumatic signal of 0.2 to 1.0 bar to operate
pneumatic actuators or reset pneumatic controllers.
The PN-VPC accepts a 2...10 Vdc / 4...20 mA signal. It
includes a voltage to current converter. The PN-VPC
requires an external 24 Vac power supply.
MAINTENANCE
A full range of maintenance programs is available from your
local registered Trend office.
SPECIFICATIONS
Type No. PN-VPC
Power supply
+10% / -15%
24 V, 50/60Hz
Power consumption 1.7 VA
Input signal 2... 10 V
Min. current at
10 Vdc
(0.1 mA)
0.02 bar (2 kPa) max. at 0 Vdc Output pressure at
1.25 bar (125 kPa)
main pressure
1.12 bar (112 kPa) min. at 11.5 Vdc
Main air pressure 1.25 bar (125 kPa)
Main air pressure
independence
1% per 0.1 bar main air pressure
Maximum safe air 2.0 bar (200 kPa)
Air consumption 42 NL/h (700 sccm) at 0.6 bar
Air capacity 720 NL/h (12000 sccm)
Air connections
Dual-barb-fittings for either 6 x
1 mm (1/4“ O.D.) or 4 x 0.75 mm
(5/32“ O.D.) polyethylene tubing.
Calibration Factory calibrated
Ambient temperature 5...55ºC
Storage -30...+70ºC
Humidity 5...95% RH
All E/P-Transducers supplied with 1 m cable
WIRING
Distance
E/P-Transducer
Type of wire length max.
to ... 100 m 150 m
Controller local standard 1.0 mm
2
1.5 mm
2
See also
Fig. 3.
NOTE: The E/P Transducer connection wire 24 V
(black) must be connected to the same potential
0 V level as the controller.
PN-VPC Data Sheet TA200855 Issue 1/B 28/03/07 1
EN0B-0505GE51 R0307B
Seitenansicht 0
1 2

Inhaltsverzeichnis

Seite 1 - EN0B-0505GE51 R0307B

PN-VPC ELECTRONIC/PNEUMATIC-TRANSDUCER PRODUCT DATA APPLICATION An E/P Transducer accepts a proportional voltage signal from an electronic cont

Seite 2 - Data Sheet

PN-VPC Data Sheet OPERATION The input signal 2...10 V is fed into a voltage to current converter in the PN-VPC. The current through the coil produces

Kommentare zu diesen Handbüchern

Keine Kommentare